Page 5 - Instruction Manual 3
P. 5
DYNODRIVE 3
the unit is powering up. To change a setting, disconnect This section describes how to install and use the Control
input power, set the switch, and then reconnect power. and DynoDrive® Motor in the most common
The OFF position is to the Left and the ON position is to configurations.
the Right (See Figure 1). Switch descriptions are given in
the following table: 1. Mount the Control
Switch: Description: OFF Setting ON Setting
2. Select a Motor
1 Rotation Direction Counter-Clockwise* Clockwise*
2 Mode ZPA/ZIP ZPA ZIP
3. Select a Speed
3 Zone Type Exit/Transport Entry/Transport
4 Target Speed 4. Configure the Location
(with SW5 & SW6)
5 Target Speed
(with SW4 & SW6) See Table 6: Operating Speed 5. Configure the Operating Mode
6 Target Speed
(with SW4 & SW5) 6. Configure the Rotation
7 Motor Selection UD048 UD060
8 Braking & ZMH Enabled Disabled 7. Configure Communications
Table 4: Configuration Switch Settings
8. Connect User Input/Output
*NOTE: The direction of rotation is defined when
viewed from the back side of the motor with the 3.1 Mount the Control
shaft extending away from the viewer.
Mount the control in a location where the motor cable
2.7 Upstream Cable Connection reaches the motor connector without putting strain on
the connector.
This RJ-25 connector is intended for use with a 6-wire
modular phone cable to connect to an adjacent upstream 3.2 Select Motor Rating Being Used
ZoneLogix control. See Section 5.3 for information on the
6-Wire Modular Cable Orientation. The Modular RJ-25 Select the motor you will be using. Properly match the
Cable is not provided. control’s motor selection to the motor that is actually
being operated by the control.
2.8 Downstream Cable Connection In addition to the standard 48 watt DynoDrive® motor,
This RJ-25 connector is intended for use with a 6-wire this control provides increased performance with our 60
watt DynoDrive motor with its higher operating speed.
modular phone cable to connect to an adjacent
downstream ZoneLogix control. See Section 5.3 for SW7: Motor: Comments:
information on the 6-Wire Modular Cable Orientation. OFF UD048 Previously 100W24
The Modular RJ-25 Cable is not provided.
ON UD060 Previously 125W24
2.9 Mounting Plate/Heat Sink Table 5: Motor Selection Switch Settings
This component is for mounting the control assembly to 3.3 Select a Speed
the conveyor frame using two ¼ inch (6.35 mm), bolts to
keep the controller cooler. Three switches determine the operating speed, making
it simple to match speeds in multiple zones. The actual
CAUTION: If mounting the control on a curved section speed selected also depends on the motor that you
of conveyor, use washers between the mounting plate selected in the previous step, so set those switches first.
and the conveyor frame. This is to assure that the There is also possible to use the 0-10Vdc differential
mounting plate is not distorted, causing damage to the Analog control input for remote, dynamic speed
enclosed printed circuit board assembly. adjustment while the system is running.
2.10 Cover Switches: Speed Selection (RPM):
SW6 SW5 SW4 UD048 UD060
CAUTION: Removal of the cover will void the warranty.
Thecover does not make the control waterproof or OFF OFF OFF 280 350
dustproof. OFF OFF ON 248 310
The cover can help reduce the severity of damage to the OFF ON OFF 216 270
control from foreign objects. OFF ON ON 184 230
3. INSTALLATION ON OFF OFF 152 190
ON
OFF
ON
150
120
ON ON OFF 88 110
GUIDE ON ON ON 56 70